Fire protection

Data centers feature fire protection systems, including passive and active design elements, as well as implementation of fire prevention programs in operations. Smoke detectors are usually installed to provide early warning of a developing fire by detecting particles generated by smoldering components prior to the development of flame.

This allows investigation, interruption of power, and manual fire suppression using hand held fire extinguishers before the fire grows to a large size. A fire sprinkler system is often provided to control a full scale fire if it develops. Fire sprinklers require 18 in (46 cm) of clearance (free of cable trays, etc.) below the sprinklers. Clean agent fire suppression gaseous systems are sometimes installed to suppress a fire earlier than the fire sprinkler system. Passive fire protection elements include the installation of fire walls around the data center, so a fire can be restricted to a portion of the facility for a limited time in the event of the failure of the active fire protection systems, such as making sure the door is not left open or if they are not installed. For critical facilities these firewalls are often insufficient to protect heat-sensitive electronic equipment, however, because conventional firewall construction is only rated for flame penetration time, not heat penetration. There are also deficiencies in the protection of vulnerable entry points into the server room, such as cable penetrations, coolant line penetrations and air ducts. For mission critical data centers fireproof vaults with a Class 125 rating are necessary to meet NFPA 75standards.